Table 1.4 Positioning control start error (100 to 199) list (Continued)
Control mode
Error
code
Positioning
Fixed-pitch feed
Speed
Speed/position switching
Speed switching
Constant-speed
JOG
Manual pulse generator
Home position return
Position follow-up control
OSC
Speed control with
fixed position stop
Error cause
Error
processing
Corrective action
140
The travel value of the
reference axis is set at "0" in
the linear interpolation for
reference axis specification.
• Do not set axis of travel value
"0" as the reference axis.
141
• The position command
device of position follow-up
control is set the odd
number.
• Set the even number for the
position command device of
position follow-up control.
142
• The positioning control which
use the external input signal
was executed for the axis
which has not set the
external input signal in the
system settings.
Set the external input signal in
the system setting.
145
Unusable instructions were
started in the external input
signal setting via servo
amplifier.
• Do not start the speed/position
switching control and count type
home position return in the
external input signal setting via
servo amplifier.
151
• Not allowed axis started in
the virtual mode. (It cannot
be started with error at real/
virtual mode switching.
152
• It started at the virtual mode
and during deceleration by
all axes servo OFF (M2042
OFF).
153
• It started at the virtual mode
and during deceleration by
occurrence of the output
module servo error.
Positioning
control
does not
start.
• Start in the virtual mode again
after correct the error cause in
the real mode.
Tartalomjegyzék