Sanyo autó tartozékok CH3642 Kézikönyv

PDF Kézikönyvek
94 Oldalak Angol

Sanyo autó tartozékok CH3642
43
S4359146
(2) Basic wiring diagram for group control
This diagram shows when several units (max. 8) are
controlled by a remote controller. In this case, a
remote controller can be connected at any indoor unit.
R.C. Address should be set before turning the power on.
Auto. address setting can be executed by a remote controller automatically.
Please refer to 12-4 “Automatic Address Setting Method”.
Each successive unit will respond at one-second intervals following the order of the R.C. address when the
remote controller is operated.
NOTE
1
2
U1
U2
11
2
1
2
1
2
G G
4
L1
L2
G
Indoor Unit
Inter-unit
power wiring
single phase
230/208V
Inter-unit
control wiring
(Low voltage)
RED
BLK
Remote controller
Outdoor Unit
Ground
Ground
(Option)
B
D
A
A
A
E
2089_M_I
Power supply
single phase
230/208V
*1
R.C. Address on the PCB: 1 (S2, BLK)
L1
L2
U1
U2
1
1
2
U1
U2
1
2
1
2
4
L1
L2
G
Indoor Unit
Inter-unit
power wiring
single phase
230/208V
Inter-unit
control wiring
(Low voltage)
Outdoor Unit
Ground
Ground
B
E
Power supply
single phase
230/208V
Power supply
single phase
230/208V
R.C. Address on the PCB: 2 (S2, BLK)
L1
L2
U1
U2
2
1
2
U1
U2
1
2
1
2
4
L1
L2
G
Indoor Unit
Inter-unit
power wiring
single phase
230/208V
Inter-unit
control wiring
(Low voltage)
Outdoor Unit
Ground
Ground
B
R.C. Address on the PCB: 8 (S2, BLK)
L1
L2
U1
U2
8
C
C
C
*Remote controller wirings are wire joint connection.
2
Kapcsolódó Kézikönyvek a Sanyo autó tartozékok CH3642